| Introduction | ||||||||||||||||||||||||||
Experts agree the most important first aid procedure for eye and skin contact with hazardous materials is abundant irrigation within seconds. The need for immediate flushing requires the installation of emergency eyewash and shower devices in accessible locations that require no more than 10 SECONDS to reach. Studies have shown there is a significant difference in the outcome of chemically burned eyes and skin tissue that receive prompt irrigation and those that did not undergo immediate flushing - patients required less surgery, had shorter hospital stays, and faster recoveries. |
||||||||||||||||||||||||||
The type of emergency eyewash and shower device, and the maintenance of that device can greatly affect the treatment and eventual recovery. Safety professionals can choose from a variety of emergency eyewash stations , emergency showers, and combination emergency eyewash and shower devices. The primary eyewash unit required for a hazard area must meet the requirements set by ANSI Z358.1-2004. Eyewash stations and bottles that supply less than the minimum flushing requirements of ANSI Z358.1-2004 are intended to support, not replace, primary units. These supplemental or personal eyewash units are referred to as secondary devices. |
||||||||||||||||||||||||||
| OSHA Regulations state in 29 CFR 1910.151: "Where the eyes or body of any person may be exposed to injurious corrosive chemicals, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use." | ||||||||||||||||||||||||||
| Another consideration for selection of emergency eyewash and emergency showers are the Material Safety Data Sheet (MSDS) for the chemicals used in your facility. The MSDS provides information about that chemical's potential health hazards and contains emergency and first aid procedures to follow immediately after exposure, until medical help arrives. The MSDS will normally state if an emergency eyewash and/or emergency shower is required | ||||||||||||||||||||||||||
OSHA enforces the ANSI Z358.1-2004 standard that contains provisions regarding the design, performance, installation, use and maintenance of various types of emergency equipment (showers, eye washes, drench hoses, etc.). |
||||||||||||||||||||||||||
| The following specifications are taken directly from the ANSI Z358.1-2004 standard | ||||||||||||||||||||||||||
| SHOWERS (Same for Stand Alone Emergency Shower and Combination Safety Stations) | ||||||||||||||||||||||||||
| Plumbed Shower: An emergency shower permanently connected to a source of potable water. | ||||||||||||||||||||||||||
Self-Contained Shower: A shower that contains its own flushing fluid, and must be refilled or replaced after use. |
||||||||||||||||||||||||||
| The specifications below are for plumbed showers only. | ||||||||||||||||||||||||||
| 1. Heads | ||||||||||||||||||||||||||
A. Positioned 82"--96" from floor. |
||||||||||||||||||||||||||
2. Valves |
||||||||||||||||||||||||||
A. Activate in 1 second or less. |
||||||||||||||||||||||||||
3. Installation |
||||||||||||||||||||||||||
A. Shower shall be located in an area that requies no more than 10 seconds to reach. |
||||||||||||||||||||||||||
4. Maintenance and Training |
||||||||||||||||||||||||||
A. Activate weekly to verify proper operation. |
||||||||||||||||||||||||||
| PERSONAL EYE WASH | ||||||||||||||||||||||||||
| A supplementary eye wash that supports plumbed units, gravity-feed units, or both by delivering immediate flushing fluid. | ||||||||||||||||||||||||||
| NOTE: Personal eye wash units can provide immediate flushing when they are located near the workstations. Personal eye wash equipment does not meet the requirements of plumbed or gravity-feed eye wash equipment. Personal eye wash units can support plumbed or gravity-feed eye wash units, but cannot be a substitute. | ||||||||||||||||||||||||||
Frequently Asked Questions |
||||||||||||||||||||||||||
|
||||||||||||||||||||||||||
| TOP SELLERS | ||||||||||||||||||||||||||
![]() |
Wall mount eye wash station has a 12" bowl and twin spray heads with flow control for safe water flow. The eye wash station spray heads have hinged head covers to keep them clean. The water is activated with a large highly visible push handle and 1/2" chrome plated brass stay open valve. | |||||||||||||||||||||||||
![]() |
The Fendall Pure Flow 1000 delivers unequaled eyewash safety, reliability, and value. This premier station features a patented system that delivers a purified, contaminant-free, and physiologically correct Eyesaline® solution from factory-sealed cartridges. Pure Flow 1000 does not require costly plumbing. It features a fluid balancing system that provides a constant fluid flow rate and stream height for the entire 15-minute flushing period required by ANSI Z358.1-2004. Pure Flow 1000 factory-sealed cartridges last up to 24 months, at least four times longer that other primary self-contained eyewash devices. | |||||||||||||||||||||||||
| Combination eye wash and emergency shower safety station. Two GS-Plus spray-type outlet heads deliver a flood of water for rinsing eyes. Emergency shower head has 10" diameter and is orange ABS plastic. Spray head assembly consists of two GS-Plus spray heads. Each head has a flip top dust cover, internal flow control and filter to remove impurities from water. Furnished with ANSI-compliant identification sign. Available with an ABS plastic or stainless steel eyewash bowl. |
||||||||||||||||||||||||||
Sources for More Information |
||||||||||||||||||||||||||
29 CFR 1910.151(c) |
||||||||||||||||||||||||||
American National Standards Institute |
||||||||||||||||||||||||||
Please Note: The information contained in this publication is intended for general information purposes only. This publication is not a substitute for review of the applicable government regulations and standards, and should not be construed as legal advice or opinion. Readers with specific questions should refer to the cited regulation or consult with an attorney. |
||||||||||||||||||||||||||